NFPA 72-2022 National Fire Alarm and Signaling Code

0 of 13 tabs placed

Tab & highlighter color code

Ch 1

Administration

Level II+

Scope, purpose, retroactivity (1.4) and the equivalency clause the AHJ leans on.

Sub-tab / find these

  • ▸1.4 Retroactivity
  • ▸1.5 Equivalency
  • ▸1.6 Units and Formulas

Highlight (ink only — no margin notes)

  • ▮1.4.4 — AHJ may apply retroactively where a distinct hazard exists
Ch 3

Definitions

Must-Have for Level I

Half of Level I questions hinge on a defined term (End-of-Line Device, Pathway, Supervisory Signal, Zone).

Sub-tab / find these

  • ▸3.3 General Definitions (alphabetical)
  • ▸3.3.x Initiating Device / Notification Appliance
  • ▸3.3.x Signal types: Alarm, Supervisory, Trouble

Highlight (ink only — no margin notes)

  • ▮Class designations cross-reference to Chapter 12
  • ▮Household vs. protected premises system definitions
Ch 7

Documentation

Level II+

Shop drawings (7.4), record of completion (7.5.6) and records retention (7.7.2) are stock exam questions.

Sub-tab / find these

  • ▸7.4 Shop Drawings
  • ▸7.5.6 Record of Completion
  • ▸7.7.2 Records retention — until next test and 1 year after

Highlight (ink only — no margin notes)

  • ▮Figure 7.8.2(a) Record of Completion form
Ch 10

Fundamentals & Power Supplies

Must-Have for Level I

Secondary power duration, 20% battery margin, FACU protection and trouble-signal behavior all live here.

Sub-tab / find these

  • ▸10.4.4 Protection of fire alarm control unit
  • ▸10.6.7.2.1 Secondary power: 24 h + 5 min (15 min EVACS), 20% margin
  • ▸10.15 Trouble signals (re-sound every 24 h)

Highlight (ink only — no margin notes)

  • ▮10.6.7.2.1 list items (1)–(5)
  • ▮10.14 Distinctive signals
Ch 12

Circuits & Pathways

Must-Have for Level I

Class A/B/C/D/E/N/X designations, survivability levels and shared pathways.

Sub-tab / find these

  • ▸12.3.1–12.3.7 Pathway Class designations (N = 12.3.6, X = 12.3.7)
  • ▸12.4 Pathway survivability Levels 0–3
  • ▸12.5 Shared pathway designations
  • ▸12.6 Monitoring integrity

Highlight (ink only — no margin notes)

  • ▮12.6.1 general monitoring-integrity requirement
  • ▮12.3 class descriptions — underline the single-fault behavior sentence in each
Ch 14

Inspection, Testing & Maintenance

Must-Have for Level I

Table 14.3.1 (visual inspection frequency) and Table 14.4.3.2 (test methods & frequency) are the most-opened pages on the exam.

Sub-tab / find these

  • ▸Table 14.3.1 Visual inspection frequencies
  • ▸Table 14.4.3.2 Test methods (sub-tab the battery, detector and NAC rows)
  • ▸14.4.4.3 Smoke detector sensitivity: 1 year, then every alternate year
  • ▸14.6 Records

Highlight (ink only — no margin notes)

  • ▮Table 14.3.1 'Weekly' rows for unmonitored control equipment
  • ▮Table 14.4.3.2 battery load-voltage test (semiannual) and discharge test (annual)
Ch 17

Initiating Devices & Spacing

Must-Have for Level I

Detector spacing, sidewall mounting, beam/sloped ceilings, heat color codes and manual box location.

Sub-tab / find these

  • ▸17.6.2.1 Table — heat detector temperature color codes
  • ▸17.7.3.2.1 Sidewall mounting within 12 in. of ceiling
  • ▸17.7.3.2.3.1 Smooth ceiling 30 ft spacing
  • ▸17.7.3.2.4.2 Beam ceilings
  • ▸17.15.5 Manual box height 42–48 in.
  • ▸17.15.8 Manual box location (60 in. of exit, 200 ft travel)

Highlight (ink only — no margin notes)

  • ▮Figure 17.6.3.1.1 / 17.7.3.2.3.2 spacing reduction figures (highlight axis labels only)
Ch 18

Notification Appliances

Must-Have for Level I

dBA rules, 110 dBA cap, 520 Hz sleeping, strobe lens height and the candela room/corridor tables.

Sub-tab / find these

  • ▸18.4.1.2 Maximum 110 dBA
  • ▸18.4.4.1 Public mode: 15 dBA above average ambient
  • ▸18.4.6.1 Sleeping: 75 dBA at pillow; 18.4.6.3 520 Hz
  • ▸18.5.5.1 Wall strobe lens 80–96 in.
  • ▸Table 18.5.5.7.1(a) Room spacing (wall-mounted)
  • ▸18.5.5.8 Corridor spacing

Highlight (ink only — no margin notes)

  • ▮Table 18.5.5.7.1(a) 20×20 / 30×30 / 40×40 / 50×50 rows
  • ▮18.4.11 Voice intelligibility
Ch 21

Emergency Control Functions

Level II+

Elevator Phase I recall, shunt trip heat detectors, HVAC shutdown, door release.

Sub-tab / find these

  • ▸21.3 Elevator Phase I emergency recall (lobby, hoistway, machine room detectors)
  • ▸21.4.2 Shunt-trip heat detector within 2 ft of each sprinkler
  • ▸21.7 HVAC systems
  • ▸21.8 Door release service / 21.9 Electrically locked doors

Highlight (ink only — no margin notes)

  • ▮21.3.x alternate recall level logic
Ch 23

Protected Premises Systems

Level II+

Positive alarm sequence timing, alarm verification, zoning, and FACU interconnection.

Sub-tab / find these

  • ▸23.8.1.3 Positive alarm sequence: 15 s acknowledge, 180 s investigate
  • ▸23.8.5.4.1 Alarm verification ≤ 60 s
  • ▸23.8.2 Interconnected FACUs

Highlight (ink only — no margin notes)

  • ▮23.8.1.3 items (1)–(4)
Ch 24

Emergency Communications (Voice)

Level III–IV

In-building fire EVACS, survivability levels for partial evacuation, intelligibility, two-way systems.

Sub-tab / find these

  • ▸24.3.14.4.1 Pathway survivability Level 2/3 for partial evacuation
  • ▸24.4.2 In-building fire EVACS
  • ▸24.5.1 Two-way in-building wired ECS (area of refuge)

Highlight (ink only — no margin notes)

  • ▮24.4.2.x message priority and live voice override
Ch 26

Supervising Stations

Level II+

Central (26.3) vs proprietary (26.4) vs remote (26.5); communication paths and runner service.

Sub-tab / find these

  • ▸26.3 Central station service
  • ▸26.4 Proprietary supervising station
  • ▸26.5 Remote supervising station
  • ▸26.6 Communications methods

Highlight (ink only — no margin notes)

  • ▮26.3 indication of central station service (placard) — underline the required marking
Annex A/B

Explanatory Material & Engineering Guide

Level II+

A.17.7.3.2.4 explains beam spacing figures; Annex B gives the detector design math for Level III–IV.

Sub-tab / find these

  • ▸Annex A explanatory notes keyed to each section (A.x.x.x)
  • ▸Annex B Engineering Guide for Automatic Fire Detector Spacing

Highlight (ink only — no margin notes)

  • ▮A.18.4.4 ambient sound level table

Section numbers follow the editions on NICET's current reference list. Verify against your own copy — editions renumber. Not affiliated with NICET or Pearson VUE.

Fire Alarm Blueprint Trainer provides educational guidance only. It does not replace professional engineering, licensed electrical work, approved fire alarm design, manufacturer installation instructions, applicable codes, or AHJ review.

© 2026 Fire Alarm Blueprint Trainer · Educational tool · Not affiliated with NFPA.