Use the code's forms: Record of Completion and Inspection & Testing

Use the code's forms: Record of Completion and Inspection & Testing

The code provides standard forms — the Record of Completion for new work and changes, and the Inspection and Testing Form for ITM — and the AHJ can require them. They capture the information the code says must be documented: system type, AHJ, monitoring arrangement, device counts, circuit classes, battery and voltage-drop results, software revision, and signatures of the installer, owner and AHJ. A contractor's own one-page 'test report' that omits half of that information is a common reason an inspector refuses to accept the ITM record.

NFPA 72 reference

Chapter 7 — Documentation

7.8 Forms (Figure 7.8.2(a) Record of Completion; Figure 7.8.2(b) Record of Inspection and Testing) — the AHJ may require these or equivalent forms; 7.5.6 Record of Completion content; 14.6.2.4 ITM form

References use NFPA 72 2019/2022 numbering — section numbers can shift between editions, so confirm in the edition your AHJ has adopted.

On the job

A county fire marshal's office receives 60 annual test reports a month in 60 formats. It issues a policy accepting only the NFPA 72 Inspection and Testing Form or a form containing every field on it. Reports that omit the device-by-device results and the supervising station transmission test are returned — and the contractors who used the code form never notice.

Quick check

1. The AHJ may require ITM documentation on:

2. The Record of Completion is signed by:

Listen to this section

AI-narrated, about a minute.

Ask about this section

Get a plain-language explanation of what this rule requires and what to check on the job.

3 free explanations left on this device.

More from this module

Fire Alarm Blueprint Trainer provides educational guidance only. It does not replace professional engineering, licensed electrical work, approved fire alarm design, manufacturer installation instructions, applicable codes, or AHJ review.