NFPA 72 code sections · Regulatory Compliance & Inspections

Impaired system? Notify, mitigate, tag, and fix on a clock

Impaired system? Notify, mitigate, tag, and fix on a clock

When any part of a fire alarm system is out of service — planned or unplanned — the owner's impairment procedures apply: the supervising station, the AHJ and the building's designated personnel are notified; mitigating measures such as fire watch are put in place as the AHJ or building code requires; a tag is placed at the control unit; and when the impairment is cleared everyone is notified again. Central station rules add that the station reports systems out of service for 8 hours or more to the AHJ. The compliance failure inspectors see most is a system that has been 'in trouble' for weeks with no one notified.

NFPA 72 reference

Chapter 10 — Fundamentals / Chapter 26

10.21 Impairments (10.21.1 notification of the AHJ and supervising station; 10.21.2 mitigation and fire watch; 10.21.3 impairment tag at the control unit; 10.21.4 restoration notification); 26.3.8 central station reporting of out-of-service systems (8 hours)

References use NFPA 72 2019/2022 numbering — section numbers can shift between editions, so confirm in the edition your AHJ has adopted.

On the job

A grocery store's NAC extender fails on a Friday. The manager silences the trouble and plans to call Monday. Saturday the fire marshal, doing a routine walk-through, sees the yellow light and asks for the impairment tag and the fire-watch log. There are none. The store gets a notice of violation and a fire-watch requirement until the repair is made.

Quick check

1. When a system is impaired, the first step is to:

2. An impaired system must carry:

3. Fire watch is:

Listen to this section

AI-narrated, about a minute.

Ask about this section

Get a plain-language explanation of what this rule requires and what to check on the job.

3 free explanations left on this device.

More from this module

Fire Alarm Blueprint Trainer provides educational guidance only. It does not replace professional engineering, licensed electrical work, approved fire alarm design, manufacturer installation instructions, applicable codes, or AHJ review.

© 2026 Fire Alarm Blueprint Trainer · Educational tool · Not affiliated with NFPA.