NFPA 72 code sections · Signal Types & Monitoring

Trouble signals must be heard, can be silenced, but can't be hidden

Trouble signals must be heard, can be silenced, but can't be hidden

A trouble condition has to produce an audible and visible indication at a location where someone can act on it — the panel or a remote annunciator where the building is attended. The audible part may be silenced, but the visible indication stays until the fault is cleared, and if a new, different trouble occurs while silenced, the sounder has to come back on (ring-back). Troubles also have to be transmitted to the supervising station when the system is monitored.

NFPA 72 reference

Chapter 10 — Fundamentals

10.15 Trouble Signals (10.15.1 indication; 10.15.6 silence with visible indication retained; 10.15.7 re-sound on subsequent trouble)

References use NFPA 72 2019/2022 numbering — section numbers can shift between editions, so confirm in the edition your AHJ has adopted.

On the job

A school custodian silences a ground-fault trouble at 6 a.m. and goes about his day. At noon a NAC opens; because the panel is programmed correctly, the trouble buzzer re-sounds and the second fault is noticed. On an older panel with ring-back disabled, the open circuit would have sat silent behind the first silenced trouble.

Quick check

1. After the trouble sounder is silenced, the visible indication must:

2. If a different trouble occurs while the first is silenced, the panel must:

Listen to this section

AI-narrated, about a minute.

Ask about this section

Get a plain-language explanation of what this rule requires and what to check on the job.

3 free explanations left on this device.

More from this module

Fire Alarm Blueprint Trainer provides educational guidance only. It does not replace professional engineering, licensed electrical work, approved fire alarm design, manufacturer installation instructions, applicable codes, or AHJ review.

© 2026 Fire Alarm Blueprint Trainer · Educational tool · Not affiliated with NFPA.