NFPA 72 code sections · Fire Alarm Design Principles

The last strobe on the circuit has to work on dead batteries

The last strobe on the circuit has to work on dead batteries

Notification appliances have a listed operating voltage range (regulated 24 V appliances are commonly listed 16-33 V). The designer calculates the voltage at the end of each NAC under worst-case conditions — all appliances in alarm, the power supply at its end-of-discharge battery voltage (about 20.4 V for a 24 V system), and the full conductor resistance both ways — and must show that the farthest appliance stays above its minimum. This is where conductor size, circuit length and appliance count get traded off; the calculation is part of the required shop-drawing submittal and the AHJ can require it be verified by measurement at acceptance.

NFPA 72 reference

Chapter 7 / Chapter 18

7.4.7 voltage-drop calculations for notification appliance circuits; 18.3.2 listed appliances operated within their rated voltage range; 10.6.7 secondary power (battery end-of-discharge as the design condition)

References use NFPA 72 2019/2022 numbering — section numbers can shift between editions, so confirm in the edition your AHJ has adopted.

On the job

A 14 AWG NAC runs 900 feet to the end of a parking garage with twelve 75-candela strobes. On paper at 24 V it works; at 20.4 V end-of-battery it falls to 14.8 V at the last strobe. The designer splits it into two circuits from a remote power supply at the midpoint rather than upsizing to 10 AWG — cheaper, and it passes the calc.

Quick check

1. The NAC voltage-drop calculation is run at:

2. Options when the last appliance falls below its minimum voltage include:

Listen to this section

AI-narrated, about a minute.

Ask about this section

Get a plain-language explanation of what this rule requires and what to check on the job.

3 free explanations left on this device.

More from this module

Fire Alarm Blueprint Trainer provides educational guidance only. It does not replace professional engineering, licensed electrical work, approved fire alarm design, manufacturer installation instructions, applicable codes, or AHJ review.

© 2026 Fire Alarm Blueprint Trainer · Educational tool · Not affiliated with NFPA.