NFPA 72 code sections · Fire Alarm System Integration

Using the building generator as secondary power — with 4 hours of battery

Using the building generator as secondary power — with 4 hours of battery

Secondary power doesn't have to be batteries alone. The code permits an engine-driven generator arranged per NFPA 110 (with a person trained to operate it on site or automatic start) as the secondary supply, provided storage batteries dedicated to the fire alarm system carry the load for at least 4 hours in the interval before the generator picks up or if it fails. Transfer to secondary power has to be automatic, the loss of primary power is annunciated as a trouble, and the fire alarm's branch circuit from the generator distribution is still dedicated and marked.

NFPA 72 reference

Chapter 10 — Fundamentals

10.6.7 Secondary Power Supply (10.6.7.1 storage battery, or automatic-starting engine-driven generator per NFPA 110 with 4-hour storage batteries; 10.6.7.2 capacity 24 h + 5 min / 15 min for EVACS); 10.6.5 dedicated branch circuit

References use NFPA 72 2019/2022 numbering — section numbers can shift between editions, so confirm in the edition your AHJ has adopted.

On the job

A high-rise designer wants to use the life-safety generator as secondary power to shrink the battery cabinets in the voice evacuation system. The AHJ agrees, provided the batteries still provide 4 hours and the panel's branch circuit comes from the life-safety generator distribution with the red-marked, labeled breaker. The battery calc drops from 24 hours to 4 hours plus 15 minutes of alarm.

Quick check

1. When a generator is the secondary power source, the fire alarm still needs batteries for at least:

2. Transfer from primary to secondary power must be:

Listen to this section

AI-narrated, about a minute.

Ask about this section

Get a plain-language explanation of what this rule requires and what to check on the job.

3 free explanations left on this device.

More from this module

Fire Alarm Blueprint Trainer provides educational guidance only. It does not replace professional engineering, licensed electrical work, approved fire alarm design, manufacturer installation instructions, applicable codes, or AHJ review.

© 2026 Fire Alarm Blueprint Trainer · Educational tool · Not affiliated with NFPA.