NFPA 72 code sections · Wiring & Circuitry

A NAC extender is a control unit: dedicated branch circuit, batteries, supervision

A NAC extender is a control unit: dedicated branch circuit, batteries, supervision

Remote power supplies and NAC extenders carry the same obligations as the main panel. Each one needs primary power from a dedicated branch circuit with the red-marked, FIRE ALARM CIRCUIT-labeled breaker, secondary power (batteries) sized for the same 24-hour standby plus alarm period, and its own monitoring for integrity — AC loss, battery trouble, ground fault and every connected NAC are supervised, and all troubles report back to the fire alarm control unit through a supervised interface. A booster that quietly loses AC and runs its batteries flat is a system that fails silently.

NFPA 72 reference

Chapter 10 — Fundamentals / Chapter 12

10.6.5 primary power (dedicated branch circuit applies to each control unit and power supply); 10.6.7 secondary power; 12.6 monitoring integrity of power supply connections and notification appliance circuits; 10.6.9 / 10.6.10 power supply supervision

References use NFPA 72 2019/2022 numbering — section numbers can shift between editions, so confirm in the edition your AHJ has adopted.

On the job

A strip mall booster is plugged into a convenience receptacle in the tenant's electrical room. A new tenant unplugs it to charge a floor scrubber; 48 hours later the booster's batteries are flat and its trouble output was never wired back to the panel. The fix: a dedicated breaker with lock-on and label, hard-wired connection, and the booster's trouble contact landed on a supervised monitor module.

Quick check

1. A remote NAC power supply must have:

2. Troubles at a remote power supply must:

Listen to this section

AI-narrated, about a minute.

Ask about this section

Get a plain-language explanation of what this rule requires and what to check on the job.

3 free explanations left on this device.

More from this module

Fire Alarm Blueprint Trainer provides educational guidance only. It does not replace professional engineering, licensed electrical work, approved fire alarm design, manufacturer installation instructions, applicable codes, or AHJ review.

© 2026 Fire Alarm Blueprint Trainer · Educational tool · Not affiliated with NFPA.