NFPA 72 code sections · Devices & Signal Flow: How the Panel Hears and Speaks

Relay module: a dry contact the panel uses to run someone else's equipment

Relay module: a dry contact the panel uses to run someone else's equipment

A relay module gives the panel a set of dry contacts it can open or close on command — nothing more. There is no supervision beyond the module itself, which is why the code says the relay must sit within 3 feet of the equipment it controls and the wiring from the panel to the relay must be monitored; the short, unmonitored jumper is kept short. Relay modules are the workhorse of emergency control functions: elevator Phase I recall and shunt trip, fan shutdown and smoke-damper closure, magnetic door holder release, unlocking access-controlled egress doors, stopping escalators or music, and giving the building automation system a 'fire alarm' status. The function, the relay and its location all appear on the input/output matrix and are tested at acceptance.

NFPA 72 reference

Chapter 21 — Emergency Control Function Interfaces

21.2.4 relay within 3 ft (1 m) of the controlled circuit or appliance; 21.2.5 monitoring of the wiring to the relay; 21.3 elevator recall, 21.7 HVAC, 21.8 door release, 21.9 electrically locked doors (typical relay-module functions); Table 14.4.3.2 emergency control functions tested

References use NFPA 72 2019/2022 numbering — section numbers can shift between editions, so confirm in the edition your AHJ has adopted.

On the job, step by step

  1. A smoke detector in the first-floor elevator lobby alarms.
  2. The panel's sequence of operation commands the relay module in the elevator machine room — mounted within 3 feet of the elevator controller — to close its recall contact.
  3. The elevator controller, not the fire alarm, performs Phase I recall and sends the cars to the alternate level because the alarm is on the designated level.
  4. A second relay module at the air handler opens the fan's run circuit; a third drops the magnetic door holders in the lobby corridor.
  5. All three functions are rows on the I/O matrix and were witnessed by the AHJ at acceptance.

Quick check

1. A relay module must be located:

2. Which is a typical relay-module function?

3. The wiring between the panel and a relay module must be:

Listen to this section

AI-narrated, about a minute.

Ask about this section

Get a plain-language explanation of what this rule requires and what to check on the job.

3 free explanations left on this device.

More from this module

Fire Alarm Blueprint Trainer provides educational guidance only. It does not replace professional engineering, licensed electrical work, approved fire alarm design, manufacturer installation instructions, applicable codes, or AHJ review.

© 2026 Fire Alarm Blueprint Trainer · Educational tool · Not affiliated with NFPA.